See HCF_SPEC-151 Common Practice Command Specification, 6.3.1 Loop Current Trim Procedure.
Commands needed to perform two point calibration of the field device's Loop Current value:
- Command 40 Enter/Exit Fixed Current Mode
- Command 45 Trim Loop Current Zero
- Command 46 Trim Loop Current Gain