See HCF_SPEC-151 Common Practice Command Specification, 6.3.1 Loop Current Trim Procedure.


Commands needed to perform two point calibration of the field device's Loop Current value:

  • Command 40 Enter/Exit Fixed Current Mode
  • Command 45 Trim Loop Current Zero
  • Command 46 Trim Loop Current Gain