History of change requests and upgrades to the HART Test System (KIT-192, TK20192) are listed herein. 


TABLE OF CONTENTS


Current Released Version


Release 3.8  September 2023

[Current version for Registration]

 

This release reflects the following HART Test Specifications:
  • HCF_TEST-001, FCG TT20001 Revision 5.1 Preliminary A
  • HCF_TEST-003, FCG TT20003 Revision 5.2 Preliminary B
  • HCF_TEST-004, FCG TT20004 Revision 7.1 Preliminary A
  • HCF_TEST-008, FCG TT20008 Revision 1.0

New Test Cases for Version 3.8:
Data Link Layer Tests:
DLL028A-B

Universal Command Tests:
UAL003C-E
UAL004
UAL005
UAL015
UAL038C
UAL048C

The following CRs were resolved in this release:

 

CR Number

Summary

Affected Components

Data Link Layer Tests

159

Removed unnecessary sleep timer. 

DLL039A

519

DLL010 and DLL011 end with unexpected termination

DLL010 & DLL011

690

DLL035: FP 280 does not check for byte count != 3

DLL035

1377

Update IdentifyDevice to Latest Test Specification

All DLL, UAL and CAL test cases.

1470DLL039A: Update Message ReportingDLL039A
1474DLL024C: Update Post Processing Call to CheckSlaveSTODLL024C
1531DLL040: Add Header Information to Device LogDLL040
1532Update Test Logs: Adjust APP / DLL Headers To Match Each Other

All DLL, UAL and CAL test cases.


Universal Command Tests

502

AppLayer: Log names for wireless test execution to be changed to ualwxxx and calwxxx

All UAL and CAL test cases.

859

UAL008: Update to Latest Test Specification

UAL008

1134

UAL011B: Warning Message Needs Updating

UAL011B

1145

Update Sequence Number Upper Bounds

All UAL and CAL test cases

1265

UAL048B: Update Failure Point Comment For 3556 & 3557

UAL048B

1365

UAL038A: Remove FP 3473

UAL038A

1376

CyclePower: Current Architecture Does Not Support HART-IP or Wireless

UAL003D, UAL038A, 

CAL071A, CAL109B, CAL524F, 

CAL526F 

 

1381

UAL038: Needs to be updated to the latest test specification

UAL038A - C

1385

UAL048: Needs to be updated to the latest test specification

UAL048A - C

1391

UAL010: Update Test Case to Latest Test Spec

UAL010

1459

UAL014: Update Private Lab Logic So Command 15 is Sent Only To HART 6.

UAL014

1464

UAL003B: Wireless Devices Failed For Retries

UAL003B

1597UAL004: Use lowercase for test nameUAL004
1618HART-Add Connect OptionALL UAL, CAL and HIP test cases

Common Practice Tests

153

CAL036: Prompt User To Set LRV To 0 and Then Wait For En

CAL036

214

CAL526F: Failure Point 11172 can incorrectly get issued.

CAL526F

302

CAL035: Report Failure Point Values

CAL035

303

CAL035: Test is not sending updated urv0

CAL035

578

CAL103C abort earlier in absence of BACKs

CAL103C

799

BURSTOFF prints incomplete msg if either hipiosys or hipnmgw is running

BURSTOFF

854

CAL104B: Update UPDATE_PERIOD To Handle ACQUISITION_PERIOD of 0xFFFFFFFF

CAL104B

1079

CAL074D: VerifyResponseAndByteCount Counts Need Updating

CAL074D

1085

CAL074B: Command 77 is Sending Incorrect Data

CAL074B

1234

CAL074D: FP 7105 Need Updating

CAL074D

1242

CAL109A: Remove FP 209 and Call DisableBurstMode

CAL109A

1332

CAL000: Command 514 HART 6 BC Needs To Accept BC 4

CAL000

1351

EnableBurstMode: Update for Wireless Adapters

All burst mode test cases

1393

CAL074A: Update Test Case to Latest Test Spec

CAL074A

1394

CAL074B: Update Test Case to Latest Test Specification

CAL074B

1401

CAL073: Update Warning Message

CAL073

1435

CAL523B: ReadCondensedStatusMap Uses Wrong Index

CAL523B

1601CAL104B: Update Failure Point MessageCAL104B
1604CAL520A: Send Command 521 With Extra ByteCAL520A
1606CAL071A: Test case should only run via fskCAL0
1610CAL104A: Add Response Code 8 to VerifyResponseAndByteCountCAL104A
1611CAL051: Remove Wireless Failure PointsCAL051

 HART-IP Server Tests

 1467

 HIP103A: Sends Invalid Inactivity Close Time

HIP103A

 1468

 HIP206: Sends Additional PDU's After NAK Received

HIP206

HART-IP Token Passing Data-Link Stack

874

Improved the burst arbitration for HIPTP 

hiptp

1425Improved Error Message Processinghiptp

HTest

875

Improved the burst arbitration for HTEST
  

htest

Known Issues

1434

Intermittent Restarting State Machine Message

 hiptp

 


Releases Accepted for Product Registration Pre-Testing

Release 3.8 - September 2023

See Release 3.8

Previous Released Versions


Version 3.8 Beta 1  March 2023


See Release 3.8

Version 3.7 Beta 2 – March 2022


Access is only available to HART-IP Beta participants only

This release reflects the following HART Test Specifications:
  • HCF_TEST-001, FCG TT20001 Revision 5.0
  • HCF_TEST-003, FCG TT20003 Revision 5.1
  • HCF_TEST-004, FCG TT20004 Revision 7.0
  • HCF_TEST-008, FCG TT20008 Revision 1.0


The following CRs were resolved in this release:

CR NumberSummaryAffected Components
Universal Command Tests
1353Update Time Out For WirelessAll UAL Tests
1359Update Command 22 MessageUAL013B
Common Practice Tests
503Burst Mode Tests must abort if DUT profile indicates wirelessHART deviceAll Burst Mode Tests
748CheckBurstCommands: FP 580 and IO DevicesAll Burst Mode Tests

1353Update Time Out For WirelessAll CAL Tests
1354Update Burst Time For WirelessCAL103A
1360Update Command 521 MessageCAL520B
1361Update Tag's With Null Characters For HART-IP / WIRELESS GATEWAYSCAL520A
HART-IP Server Tests
1345Update Failure PointHIP202B
1346Add Cleanup ProcedureHIP102
1347Update MSG ID To Follow Updated Test SpecHIP202B
1349Failure Point 750 / Update Printing Of Byte CountHIP303014
1350Failure Point 702 Needs To Check Longitudinal Parity ErrorHIP303009
1352Update Command 1 Embedded AddressHIP303015


Version 3.7 Beta 1 – November 2021

Access is only available to HART-IP Beta participants only

This release reflects the following HART Test Specifications:
  • HCF_TEST-001, FCG TT20001 Revision 5.0
  • HCF_TEST-003, FCG TT20003 Revision 5.1
  • HCF_TEST-004, FCG TT20004 Revision 7.0
  • HCF_TEST-008, FCG TT20008 Revision 1.0

New test cases developed to verify HART-IP compliance.

 

In addition to new the new test cases listed below the HART-IP Client has been enhanced for communication over TCP and IPv6 Protocols.

 

HART-IP Server Tests:

  • HIP101
  • HIP102
  • HIP103A
  • HIP103B
  • HIP103C
  • HIP103D
  • HIP202A
  • HIP202B
  • HIP203
  • HIP204
  • HIP205
  • HIP206
  • HIP301
  • HIP302A
  • HIP302B
  • HIP303002
  • HIP303003
  • HIP303004
  • HIP303005
  • HIP303006
  • HIP303007
  • HIP303009
  • HIP303012
  • HIP303014
  • HIP303015
  • HIP303024A
  • HIP303024B
  • HIP303024C
  • HIP303032
  • HIP303033A
  • HIP303033B
  • HIP303042
  • HIP304A
  • HIP304B
  • HIP305A
  • HIP305B
  • HIP305C
  • HIP401
  • HIP402

Common Practice Command Tests:

  • CAL520A
  • CAL520B
  • CAL532A
  • CAL532B
  • CAL538A
  • CAL543A
  • CAL543B

 

Universal Command Tests:

  • UAL003A
  • UAL003B
  • UAL013A
  • UAL013B
  • UAL014

The following CRs were resolved in this release:
Universal Command Tests
CR NumberSummaryAffected Components
#776Update Reported Final ResultAll UAL Tests
Common Practice Tests
#776Update Reported Final ResultAll CAL Tests
#1249Burst Message CausingCAL109B
#1257Add HART-IP PeriodsCAL103A
#1274Remove Command 42CAL042, CAL071A-B, CAL109B, CAL524F, CAL526F
#1277Adjust Trigger Value to ! and - 10%CAL104B
#1331CAL000: Add HART-IP Command RC & BCCAL000


Release 3.6 - October 2019  

This release reflects the following HART Test Specifications:
  • HCF_TEST-001, FCG TT20001 Revision 4.0
  • HCF_TEST-003, FCG TT20005 Revision 4.1
  • HCF_TEST-004, FCG TT20004 Revision 6.0

New CAL test cases shall implement burst-mode testing (formerly DLL test cases).
  • DLL036A,B,C,D -> CAL108A,B,C,D
  • DLL037A,B,D -> CAL109A,B,C
  • DLL043A,B -> CAL107A,B
  • DLL045A -> CAL103A
  • DLL044A -> CAL103B
  • DLL044B -> CAL103C
  • DLL045B -> CAL104A
  • DLL045C -> CAL104B

The following CRs were resolved in this release:
Date Link Layer Tests
CR NumberSummaryAffected Components
#205Change Message Length To 0x14DLL028
#3758create consistent results statementsAll DLL Tests
#4905DLL002 incorrectly fails HART 5 devicesDLL002
#5891FindNextDeviceVariable: FP 5146All DLL Tests
#5256DLL009 failure point 702 valid check byte inadvertently sent in messageDLL009
#5419DLL015 overflow of device type codeDLL015
#5431DLL038 Cannot read data at offset 30 Msg data has only 24 bytes!!DLL038
#5698DLL028 Test in HTEST Kit 3.3 incorrectly passes the Device.DLL028
#5730DLL033D: Script may fail wireless deviceDLL033D
#5731DLL033D: PP may fail wireless deviceDLL033D
#5831CheckSlaveSTO / Command 256 response in DLL024CDLL024C
#5865DLL028: Add 1 tick to RT1DLL028
#5883DLL033A-D: IssueCommand6 Needs to be implementedDLL033A-D
#5884DLL033A-D: IssueCommand6 Needs to be implementedDLL033A-D
#5891FindNextDeviceVariable: FP 5146DLL018
#5897DLL018: FP 277 & 796 are not being triggered as intendedDLL018
#5899DLL033D: FP 538 message missing parametersDLL033D
#5986DLL018: Needs to fail for an empty dVar listDLL018
Universal Command Tests
#3759create consistent results statementsAll UAL Tests
#2666UAL010 - Test states DUT power was not removedUAL010
#2812UAL000 test for command 31UAL000
#5679UAL048B: Automation need to be updated to match r4.2 of TEST-003UAL048B
#5735UAL001 failure point 2126 on NaN loop current valueUAL001
#5878UAL009: Dispatching CMD48 inconsistent with Test SpecUAL009
#5955UAL009: Update getLine function not to grab '\n' characterUAL009
#5956UAL048B: Add fp if MSA is not setUAL048B
#5962UAL009: VerifyResponseAndByteCount verifying wrong Byte CountUAL009
#5990UAL011A must find at least 1 dVarUAL011A
#5999UAL011A must be device var for Cmd 3 dynamics UAL011A
#6002No Connection Stack OverflowAll UAL Tests
#6007Add delay before sending wireless messageAll UAL Tests
#6008messaging performance degraded from v3.5All UAL Tests
Common Practice Tests
#3757create consistent results statementsAll CAL Tests
#5546CAL523A fails when command not implementedCAL523A
#5600CAL072 Squawk must test invalid selectionCAL072
#5619CALU526F gives a false PassCALU526F
#5626CAL051 does not account for HART 5 devicesCAL051
#5682CAL033: FP 6301 missing Unit Code 254CAL033
#5683CAL053: FP6690 not check unit code 254CAL053
#5688CAL524B: Test automation needs to be updated to the latest HCF_TEST-004CAL524B
#5728CAL053 fails for RC = BusyCAL053
#5739CAL523C: fp 7937 Assumes MAINTENANCE REQUIRED bit must be setCAL523C
#5749CAL052 fails on update failureCAL052
#5786CAL524B: FP 11014 Remove CommentCAL524B
#5817Command 109: Does Not Set Burst Message Field CorrectlyAll CAL Tests
#5819Command 105: Need updating to HART 7All CAL Tests
#5820Command 108: Needs updating to HART 7All CAL Tests
#5821Command 107: Needs updating to HART 7All CAL Tests
#5823Time Class: Needs a function to update timeAll CAL Tests
#5836FieldDevice Class: Add device profile variableAll CAL Tests
#5841CheckForCommand: Need new message objectAll CAL Tests
#5861FindNextDeviceVariable: FP 5142All CAL Tests
#5873CAL524B Expected value should be changedCAL524B
#5896FindNextDeviceVariable: FP 5146All CAL Tests
#5920CAL035: FP 6386 checking wrong urvCAL035
#5928CAL523B: FP 7890 Cancatenated Data Field IssueCAL523B
#5942CAL523B: Reference to Table 22 is incorrect.CAL523B
#5959CAL000: Command 528 Byte CountCAL000
#5973CAL523C: Test fails when Status Bit not Set.CAL523C
#5979CAL000: HART 6 needs to accept BC == 4 on RC == 0x40CAL000
#6002No Connection Stack OverflowAll CAL Tests
#6007Add delay before sending wireless messageAll CAL Tests
#6008messaging performance degraded from v3.5All CAL Tests
#6010Provision: Change case of first letterProvision
HSniffer
#5745Add Command Line OptionsHSniffer
#5784HSniffer: Reporting GAP / PARITY / FRAMING ErrorsHSniffer
#5859Cleanup HeadersHSniffer
#5862Test Case Bash Scripts Command LineHSniffer
Known Issues
#5617CAL071B results confusing for wireless deviceCAL071B
#5951CAL071B: Test needs to be modified to work with new architectureCAL071B
#5604UAL000 .out file does not match test logUAL000
#5598DLL040 Move continue test questionDLL040


Release 3.5 - October 2017

This release reflects the following HART Test Specifications:
  • HCF_TEST-001, FCG TT20001 Revision 3.1
  • HCF_TEST-003, FCG TT20005 Revision 4.1
  • HCF_TEST-004, FCG TT20004 Revision 5.0


The following CRs were resolved in this release:
CR NumberSummaryAffected Components
3630Does not send parity errorsDLL028
5407Private Label Distributor value from Command 0DLL032
5608FP1012 should allow Success or ConflictDLL045B
5792Test logs show incorrect HW versionAll DLL Tests
3775Classification conflict with Command 9. For Command 8, "0" is the expected classification code for unsupported or undefined variable codes. The test automation has been updated to TEST-003 {4.1}.UAL012
3999Cannot compare NAN valuesUAL011b
5624FP 3262 fails on equal NaN valuesUAL011B
5649Send consistent number of dvarsUAL011B
5737Failure point 3258 on NaN loop current valueUAL011B        
5748Fails due to ConfigChangedCounter checkUAL009
5789Test logs show incorrect HW versionAll UAL Tests
5797FP 3224 is redundantUAL011A
5804Does not xOr bytesUAL006
5606Tests can get caught in an endless loopCAL523C
5686Update message at FP 7890CAL523B
5717Script expecting incorrect map code on command 524 responseCAL524B
5720extra map codes are being sent failure point 11014CAL524B
5729FP11001 is checking wrong map codeCAL524A
5737Failure point 3258 on NaN loop current valueUAL011B
5791Test logs show incorrect HW versionAll CAL Tests
5815Update for quickly bursting devicesDLL028
5829FP 3249 testing incorrect variableUAL011B
5834UDP not behaving correctly according to test specAll UAL & CAL Tests
     Known issues 
#5604.OUT file does not match test logUAL000
#5617Test results confusing for wireless deviceCAL071B
#5619Test case gives a false PassCALU526F
#5620Test case causes subsequent tests not to be executedCALU526F
#5598Move continue test questionDLL040
#5256Failure point 702 valid check byte inadvertently sent in messageDLL009
#5841Need new message objectCheckForCommand library function
#5599FP 508 Not Following Test SpecificationDLL033C
     Operational issues
#5741Command 104 Needs to use LTL & UTLDLL045C


Patch for Release 3.3 - June 2017

The following CRs were resolved in this patch:

  • #5597 - CAL526D: FP 11153 is a duplicate
  • #5648 - Review UAL009 FP 2987
  • #5656 - DLL044B test automation trigger units incorrect
  • #5675 - FindNextDeviceVariable skips of dvar with dvar.Units == 251 or 253
  • #5685 - CAL524B: Is not sending map codes 0x07, 0x03
  • #5691 - CAL526C: Test is not sending Command 48
  • #5705 - UAL038A: FP 3472 Test writing original message
  • #5716 - CAL526C: Typo in FP Message (RE: DEVICE_STATUS_SIMULATED, FP11145)


References:
  • HCF_TEST-001, FCG TT20001 [Revision 3.1]
  • HCF_TEST-003, FCG TT20005 [Revision 4.1]
  • HCF_TEST-004, FCG TT20004 [Revision 5.0]
Known issues to be resolved in the next release include:

HART Technology WG has reviewed and concurred that Command 8 must align with precedent in Command 9.

Dynamic Variables not supported by the device need to return 0 "Not Yet Classified" for Command 8.

UAL012 fails when SV or TV (correctly) return zero in the Command 8 response when SV or TV are not supported by the device. Command 8 response will require manual verification.

See CR#3775 and #3275. 


Release 3.3 - March 2017

The following changes are included in this release:
  • Installation of version 3.3 requires the existing installed version to be v3.0 or higher.
  • Improved Token-Passing Data-Link test automation
  • Improved Universal Command test automation
  • Improved Common Practice Command test automation
  • New (beta) Condensed Status Tests
  • Improved HSniffer utility
  • New Scripts added


Slave Token-Passing Data-Link Layer Tests
New Tests:
  • DLL033D
  • DLL045A (verify the compliance Command 103)
  • DLL045B (verify the compliance Command 104)
  • DLL045C (verify the compliance Smart Publishing)
Updated Tests:
DLL001A DLL001B DLL001C DLL001D DLL001E DLL001F DLL002 DLL003 DLL004 DLL005 DLL006 DLL007 DLL009 DLL010 DLL011 DLL012 DLL014 DLL015 DLL016 DLL017 DLL018 DLL019 DLL020 DLL021 DLL022 DLL023 DLL024A DLL024B DLL024C DLL025 DLL026 DLL027 DLL028 DLL029 DLL030 DLL032 DLL033A DLL033B DLL033C DLL034 DLL035 DLL036A DLL036B DLL036C DLL036D DLL037A DLL037B DLL037C DLL037D DLL038 DLL039A DLL039B DLL040 DLL041 DLL042 DLL043A DLL043B DLL044A DLL044B

Issues Resolved:
#3618 #3634 #3799 #4098 #4130 #4266 #4348 #4352 #4389 #4436 #4585 #4625
#4714 #4921 #4979 #5033 #5056 #5057 #5058 #5069 #5075 #5076 #5148 #5160
#5161 #5182 #5191 #5192 #5193 #5209 #5248 #5251 #5256 #5259 #5261 #5264
#5282 #5305 #5308 #5316 #5317 #5359 #5386 #5397 #5398 #5399 #5400 #5401
#5402 #5403 #5404 #5406 #5410 #5412 #5413 #5415 #5418 #5426 #5429 #5450
#5461 #5465 #5486 #5533 #5554 #5556 #5565 #5566 #5567 #5570 #5587 #5588

Universal Command Tests
Updated Tests and Scripts:
UAL000 UAL001 UAL005 UAL006 UAL007 UAL008 UAL009 UAL010 UAL011A UAL011B UAL012 UAL013 UAL038A UAL038B UAL048A UAL048B

Issues Resolved:
#2737 #2667 #2790 #3775 #3886 #4037 #4131 #4263 #4581 #4603 $4659 #4708
#4715 #4764 #5169 #5170 #5195 #5199 #5201 #5210 #5250 #5298 #5357 #5432
#5439 #5440 #5447 #5451 #5463 #5506 #5507 #5528 #5534 #5542 #5543 #5546
#5548 #5560 #5563 #5571 #5575 #5576 #5577 #5578 #5581 #5585

Common Practice Tests 
New Tests:
CAL523A CAL523B CAL523C CAL524A CAL524B CAL524C CAL524D CAL524E CAL524F CAL526A CAL526B CAL526C CAL526D CAL526E CAL526F

A total of fifteen new test cases that test Condensed Status functionality have been added. The CAL523, CAL524, CAL526 series tests are in a Beta state.


Updated Tests:
CAL000 CAL033 CAL034 CAL035 CAL036 CAL037 CAL040 CAL041 CAL042 CAL043 CAL044 CAL045 CAL046 CAL047 CAL049 CAL050 CAL051 CAL052 CAL053 CAL054 CAL055 CAL056 CAL071A CAL071B CAL072 CAL073 CAL074A CAL074B CAL074C CAL074D

Issues Resolved:
#3191 #4132 #4371 #4551 #4796 #5072 #5150 #5154 #5184 #5198 #5214 #5225
#5272 #5304 #5358 #5438 #5447 #5449 #5451 #5462 #5470 #5491 #5494 #5512
#5518 #5522 #5527 #5528 #5529 #5534 #5535 #5542 #5543 #5545 #5546 #5560
#5590 #5614


HSniffer
Issues Resolved:
#5454 #5531 #5532 #5550



Known issues to be resolved in the next release include:


#5617 - CAL071B results confusing for wireless device

#5606- CAL523C endless loop
  • If the device replies with RC 0x02 the test will continue in an endless loop. To manually override the test execution, press CTRL+C to continue. 
  • Manual inspection required to verify results

#5597 - CAL526D FP 11153 is a duplicate and will be replaced with FP 11163.

#5619 - CALU526F gives a false Pass

#5620 - CALU526F causes subsequent tests not to be executed due to the device not being alive on the network.

#5599 - DLL033C FP 508 Not Following Test Spec

#5598- DLL040 Move continue test question
  • User should select "y" to continue the test, else the test exists prematurely

#5604 - UAL000 .out file does not match test log


Release 3.2 - December 2015

The following changes are included in this release:
  • All QA/QC processes on this HART Test System are complete, including regression tests confirming proper operation of each Failure Point (FP) in corresponding HART Test Specifications.
     
  • Detailed lists of updated test automation and improved scripts for Slave Token-Passing Data-Link Layer, Universal Command, and Common Practice Command tests are listed below.


Slave Token-Passing Data Link Layer Tests
Improvements to the Token-Passing Data Link Layer tools include the resolution of the following HCFTracker change requests were resolved: #3268, #3760, #4164, #4171, #4268, #4269, #4283, #4295, #4296, #4359, #4360, #4586, #4594, #4651, #4687, #4741, #4766, #4805, #4806, #4816, #4867, #4905, #4981, #5002, #5005, #5014, #5023, #5053, #5125, #5133. Resolution of these change requests resulted in improvements to the following tests: DLL002, DLL010, DLL016, DLL019, DLL022, DLL024B, DLL024C, DLL026, DLL027, DLL029, DLL035, DLL037D, DLL039A, DLL039B, DLL040, DLL043A, DLL043B, and DLL045. Improvements were also made to testdll and testdlludp.

In addition, improvements to HSniffer were made to optimize performance and enhance integration with the HART Test System.

Universal Command Tests
Improvements to the Universal Command Tests include the resolution of the following HCFTracker change requests: #4636, #4681, and #4689. Resolution of these change requests resulted in improvements to the following tests: UAL000 and UAL009. Improvements were also made to testual and testualudp.

Common Practice Command Tests
Improvements to the Common Practice Command Tests include the resolution of the following HCFTracker change requests : #3168, #4248, #4329, #4551, #4559, #4574, #4575, #4591, #4592, #4656, #4666, #4667, #4684, #4701, #4719, #4738, #4743, #4794, #4796, #4801, #4917, #4962, #5027, #5079, #5096, #5104, #5105, #5118, and #5167. Resolution of these change requests resulted in improvements to the following tests: CAL000, CAL040, CAL042, CAL044, CAL045, CAL046, CAL047, CAL050, CAL053, CAL054, CAL055, CAL056, CAL071A, CAL071B, and CAL072. Improvements were also made to testcal and testcaludp.



Known issues to be resolved in the next release include:


#4714- DLL033C not properly testing Loop Current, Command 6
  • Send Command 6 with 1 data byte to change Polling Address to 0 --> Loop Current Mode must be set to 0x01. This is currently manually tested.


#4979, #5357, #5358, #5407- Need to parse all Command 0 fields
  • Private Label code is not verified via automation. Must not be 0x0000. Must match Manufacturer ID unless it is private labeled product. This is currently manually tested.
  • Device Profile code is not verified via automation. Must not be 0x00. Must use Device Profile Code from Common Tables. This is currently manually tested.

#5298 - UAL038A should poll for device like UAL010

#5304- CAL033, CAL052 - CAL056 Macro findNextDeviceVariable
  •  findNextDeviceVariable must update to the Slave Common Practice Command Test Specification (HCF_TEST-004 r4.1).


#5305- DLL035 does not correctly handle RC == 8
  • Command 59 request with value 21 preambles or greater must receive a device response with Response Code of error "Passed Parameter Too Large" (RC == 3) or warning "Set To Nearest Possible Value" (RC == 8). If the DUT responds with the warning it can be mistakenly failed with "Faildll035354DLL035, Insufficient STX's detected. Failure Point==354".


#5308- DLL044A Failure Point == 951 BACK Count
  • Increase tolerance to 5% (i.e. ABS(cmd9 - cmd3) < 5 = PASS)


#5316- DLL035: Failure Point == 888 fails a DUT with the correct Byte Count
  • Command 59 request with value 1 in the data field must receive a device response with Response Code of error"Passed Parameter Too Small" (RC == 4) or warning"Set To Nearest Possible Value" (RC == 8). If the device returns RC == 8 then the preamble count must be 5. However, the automation fails a device that responds with 5 preambles.


#5317- DLL026: Failure Point == 408 Fails DUT when it returns Command 2, RC == 8
  • Add RC == 8 (Update Failure) to the list of accepted response codes that will not trigger Failure Point == 408.


#5320 - DLL033C: Add verification the correct "Loop Current Mode" is set based on the POLL_ADDRESS that was written.


#5391- DLL033C: Verify command 7 matches command 6 response
  • The test must send command 7 to verify the Loop Current Mode matches between command 6, command 7, and the device status. These three items must remain consistent. This is currently manually tested.


#5438- CAL071B: Does not properly exit for Response Code "Command Not Implemented" RC == 64
  • Test must abort if it encounters Failure Point 5125 or 5126 



Release 3.0 - August 2014

Major revision update

Release 2.3 - March 2014

Last minor version update before Release 3.0

Release 2.1 - June 2012

Hardware processor change (Atom)        

Release 1.5 - March 2010

Summary of changes over previously released version (bug #s are listed
where applicable):

Data Link Layer
* DLL019
- (#2966) This test was terminating early, before sufficient BACK
messages were acquired and incorrectly causing the device to fail.
* DLL032
- (#3030) This test was checking the entire byte value, rather than
the bit field. This could incorrectly fail a wireless device.
* DLL033a
- (#2997) This test had an erroneous failpoint 350.
- (#3146) A queue initialization error in the QAS script inhibited
the command 6's from issuing properly.
* DLL033c
- (#3038, 3090) The Loop Current Fixed bit from the Device Status
byte was not detected correctly in the post processing.
- (#2999,2995) The draft spec and the test automation had deficiencies
related to logic for Loop Current Enabled handling, which have been
thoroughly reviewed and fixed.
* DLL038
- (#3141) The post processing for this test now checks the revision
number correctly.
* DLL039a
- (#3149) This test was updated to only emit 20,000 messages for a
wireless device being tested over a maintenance port.
* DLL040
- (#2889) The post processing on this multi-drop test now correctly
handles cold start bit.

Application Layer (v1.5)

* All Tests
- Token-Passing over FSK connections is enhanced.
- New -v command line option prints test name and version.
* UAL000
- (#2812) The processing of command 31 is corrected.
* UAL048
- (#3126) The test is divided into two tests, UAL048a and b.
- (#3127) Command 48 data handling corrected.
* CAL000
- (#3091) Command 105 byte counts corrected
- (#3030, #3031) Command 75 and 77 for wireless adapters via FSK
* CAL044
- (#3157) PV Units code handling for codes 250 to 255
* CAL074d
- (#2873) Command 94 not required

HTEST (v1.4)
* (#3003) Modified the library function script_sleep() to enable it to
sleep for longer intervals.

HARTMENU (v1.4)
* (#3239) Modified to reflect updated UAL tests list.

Release 1.4 - October 2009

Summary of changes over previously released version (bug #s are listed
where applicable):

Data Link Layer
* All Tests
- (#2589) DLL tests now support command 109 returning "Invalid Selection"
for wireless devices bursting only on the TDMA channel.
* DLL001e, DLL033a
- (#2726) These tests have been modified so that the DUT can use poll
addresses other than 0. Previously, these tests would fail the DUT
unnecessarily.
* DLL003
- This test requires devices to correctly frame messages that use
expansion bytes. The failures have been changed to warnings.
* DLL018, DLL024a, DLL026
- (#2679) HART 7 devices may return response code 14 indicating warning
that dynamic variables were used in place of device variables. The
post processing has been corrected so that code 14 is allowed for
HART 7 devices.
* DLL024c
- (#2902) The error string for failure point 435 is now printing correctly.
* DLL038
- (#2905) the HART spec allows a DUT to return a buffer overflow
indication if a message it receives is too long for its buffers.
This test uses command 22 to write a long tag to the DUT and one of
the variations sends a long tag plus one data byte. This can overflow
the buffers on some devices. The Test spec and automation have been
corrected to allow "Buffer Overflow" in this situation.
- (#2802) The test handles broadcast addressing correctly.
* DLL040
- (#2590) The QAS script was updated to support 16-bit manufacturer id
and expanded device types. The post processing is now correctly
counting the number of devices on the bus. A defect remains that
may keep a HART 7 device from passing the test.
* DLL042
- (#2889) The post processing now correctly handles response codes
"Success" and "Invalid Expanded Command Number" near failure point 243.

Application Layer (v1.4)
* All Tests
- The operation of the Token-Passing has been enhanced. It is possible
to stop a running test with a Ctrl-C and to re-size a terminal window
without killing the program inadvertantly.
* UAL000
- (#2811, 2812) The processing of command 31 is added to the test.
* UAL001
- (#2852) The test specification and automation program are corrected
for the loop current on wireless devices.
* UAL007
- (#2803) This test now examines the analog channel input flags.
* UAL011a
- (#2912, 2913) Devices that return 0x00 for Max Device Variable
supported (byte 13 of command 0 response) must respond to device
variables 0, 1, 2, 3. (PV, SV, TV, QV). The test now allows
"Dynamic variables Returned for Device Variables" in this case.
- (#2990) An "Invalid Selection" response is also accepted.
* UAL011b
- (#2904) Floating point comparisons for the PV have been enhanced to
use the upper and lower range limits as a context for the floating
point comparison.
* UAL013
- (#2837) The test now allows a buffer overflow status when command 22
is issued with an extra data byte.
* UAL038b
- (#2804) This test now aborts for hart 5 and 6 devices. Earlier, the
test was being incorrectly applied to such devices.
* CAL000
- (#2833) The test vectors for this automation were upgraded for
commands above command 90 for HART 5,6 and 7.
* CAL033
- (#2957) This test now correctly counts device variables in some
situations that it did not, previously. Floating point comparisons
for the PV have been enhanced to use the upper and lower range limits
as a context for the floating point comparison.
* CAL034
- (#2935) The checking for recommended commands at the beginning of
the automation has been corrected.
* CAL035
- (#2702) This test now allows "Invalid Units" response code to be
returned from command 35.
* CAL036
- Floating point comparisons for the PV have been enhanced to use the
upper and lower range limits as a context for the floating point
comparison.
* CAL071b
- (#2958) The test now processes a command 12 response correctly.
* CAL074a,b,c,d
- (#2871) This test now aborts for adapter being tested on a TP network.
* CAL074d
- (#2873) The test now aborts if command 94 is not implemented, as
command 94 is recommended but not required for wireless adapter.

HTEST (v1.3)
* Added the following new library functions to enable easier retrieval
of information from responses received from a device:
- get_byte_count()
- get_resp_code()
- get_response()

* (#2892) Added signal handler to capture linux signal received when a
terminal window is resized.

HARTMENU (v1.3)
* (#2909) Modified to reflect available test list correctly.

Release 1.3 - July 2009


Release 1.0  - February 2009

First automated test system available